Case Study: PRESTO W56 Process system

Cooling a Büchiglas 100 l reactor from +20 °C to -20 °C with a PRESTO W56 Process system

Objective

This case study tests the cooling capacity of the JULABO PRESTO W56 Process system with a 100 l glass reactor. The PRESTO W56 is connected to the reactor via two 2 m long metal hoses. The PRESTO W56 Process system has been programmed to cool down from +20 °C to -20 °C.

Test Conditions

Product PRESTO W56 Process system
Cooling capacity (Ethanol)
°C 20 0 -10 -20 -30 -40 -50
kW 25.8 23.1 16.9 11.5 7.1 3.5 1.4
Heating capacity 27 kW
Pump pressure 0.5 bar
Duration 53 hr:min
Test volume 75 l
Setpoint 1 +20 °C
Setpoint 2 -20 °C
Reactor 100l Büchiglas (glass)
Tubing length 2 m
Fluid in unit Thermal HL60
Fluid in reactor Thermal HL60

Environment

Room temperature 20 °C
Humidity 45 %
Voltage version 400V/3PPE/50Hz

Control Parameters

XP 0.2 K
TN 695 s
TV 85 s
XPU 15 K

Test Results

The PRESTO W56 Process system cools the reactor from +20 °C to -20 °C in 53 min.