Case Study: PRESTO A80t Process system

Cooling a Asahi 20 l reactor from +50 °C to +20 °C with a PRESTO A80t Process system

Objective

This case study tests the cooling capacity of the JULABO PRESTO A80t Process system with a 20 l glass reactor. The PRESTO A80t is connected to the reactor via two 1 m long metal hoses. The PRESTO A80t Process system has been programmed to cool down from +50 °C to +20 °C.

Test Conditions

Product PRESTO A80t Process system
Cooling capacity (Ethanol)
°C 200 100 20 0 -20 -30 -40 -60 -80
kW 1.2 1.2 1.2 1.2 1.1 1.1 1.1 0.65 0.1
Heating capacity 2.8 kW
Pump pressure 0.5 bar Band limit °k
Duration 1:00 hr:min Test volume 19 l
Setpoint 1 +50 °C Setpoint 2 +20 °C
Reactor 20l Asahi (glass) Tubing length 1 m
Fluid in unit Thermal HL80 Fluid in reactor Thermal HL80

Environment

Room temperature 20 °C
Humidity 45 %
Voltage version 208V/60Hz
PRESTO A80t details

Test Results

The PRESTO A80t Process system cools the reactor from +50 °C to +20 °C in 1:00 h.

  • Set point
  • Temperature in the application
  • Temperature in temperature control unit