Case Study: PRESTO A80 Process system

Cooling a Asahi 20 l reactor from +50 °C to 0 °C with a PRESTO A80 Process system

Objective

This case study tests the cooling capacity of the JULABO PRESTO A80 Process system with a 20 l glass reactor. The PRESTO A80 is connected to the reactor via two 2 in. long metal hoses. The PRESTO A80 Process system has been programmed to cool down from +50 °C to 0 °C.

Test Conditions

Product PRESTO A80 Process system
Cooling capacity (Ethanol)
°C 20 0 -20 -40 -60 -80
kW 1.2 1.2 1.1 1.1 0.65 0.1
Heating capacity 1.8 kW
Pump pressure 5.8 psi
Duration 1:20 hr:min
Test volume 18 l
Setpoint 1 +50 °C
Setpoint 2 0 °C
Reactor 20l Asahi (glass)
Tubing length 2 in.
Fluid in unit Thermal HL80
Fluid in reactor Thermal HL80

Environment

Room temperature 20 °C
Humidity 45 %
Voltage version 230V/50Hz

Test Results

The PRESTO A80 Process system cools the reactor from +50 °C to 0 °C in 1:20 h.

Set point
Temperature in the application
Temperature in temperature control unit