Case Study: PRESTO W55 Process system
Cooling a Büchiglas 50 l reactor from +150 °C to +20 °C with a PRESTO W55 Process system
Objective
This case study tests the cooling capacity of the JULABO PRESTO W55 Process system with a 50 l glass reactor. The PRESTO W55 is connected to the reactor via two 2 in. long metal hoses. The PRESTO W55 Process system has been programmed to cool down from +150 °C to +20 °C.
Test Conditions
| Product | PRESTO W55 Process system | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Cooling capacity (Ethanol)
|
|||||||||||||||||
| Heating capacity | 15 kW | ||||||||||||||||
| Pump pressure | 7.3 psi | ||||||||||||||||
| Duration | 53 hr:min | ||||||||||||||||
| Test volume | 35 l | ||||||||||||||||
| Setpoint 1 | +150 °C | ||||||||||||||||
| Setpoint 2 | +20 °C | ||||||||||||||||
| Reactor | 50l Büchiglas (glass) | ||||||||||||||||
| Tubing length | 2 in. | ||||||||||||||||
| Fluid in unit | Thermal HL60 | ||||||||||||||||
| Fluid in reactor | Thermal H20S | ||||||||||||||||
Environment
| Room temperature | 20 °C |
|---|---|
| Humidity | 45 % |
| Voltage version | 400V/3PNPE/50Hz |
Control Parameters
| XP | 0.1 K |
| TN | 385 s |
| TV | 21 s |
| XPU | 12 K |
Test Results
The PRESTO W55 Process system cools the reactor from +150 °C to +20 °C in 53 min.
| Set point |
| Temperature in the application |
| Temperature in temperature control unit |