Case Study: PRESTO W56 Process system

Cooling a Büchiglas 100 l reactor from +20 °C to lowest possible temperature with a PRESTO W56 Process system

Objective

This case study tests the lowest temperature of the JULABO PRESTO W56 Process system with a 100 l glass reactor. The PRESTO W56 is connected to the reactor via two 2 m metal hoses. The PRESTO W56 Process system cools from +20 °C to -48.40 °C maximum low temperature.

Test Conditions

Product PRESTO W56 Process system
Cooling capacity (Ethanol)
°C 20 0 -10 -20 -30 -40 -50
kW 25.8 23.1 16.9 11.5 7.1 3.5 1.4
Heating capacity 27 kW
Pump pressure 0.5 bar Band limit °k
Duration 6:06 hr:min Test volume 75 l
Setpoint 1 +20 °C Setpoint 2 -55 °C
Reactor 100l Büchiglas (glass) Tubing length 2 m
Fluid in unit Thermal HL60 Fluid in reactor Thermal HL60

Environment

Room temperature 20 °C
Humidity 45 %
Voltage version 400V/3PPE/50Hz

Control Parameters

XP 0.2 K
TN 695 s
TV 85 s
XPU 15 K
PRESTO W56 details

Test Results

The PRESTO W56 Process system cools the reactor from +20 °C to the lowest temperature of -48.40 °C in 6:06 h.

  • Set point
  • Temperature in the application
  • Temperature in temperature control unit