Case Study: PRESTO W92tt Process system
Cooling a Büchiglas 100 l reactor from +20 °C to 0 °C with a PRESTO W92tt Process system
Objective
This case study tests the cooling capacity of the JULABO PRESTO W92tt Process system with a 100 l glass reactor. The PRESTO W92tt is connected to the reactor via two 3 m long metal hoses. The PRESTO W92tt Process system has been programmed to cool down from +20 °C to 0 °C.

Test Conditions
Product | PRESTO W92tt Process system | ||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Cooling capacity (Ethanol)
|
|||||||||||||||||||||
Heating capacity | kW | ||||||||||||||||||||
Pump pressure | 0.5 bar | ||||||||||||||||||||
Duration | 1:00 hr:min | ||||||||||||||||||||
Test volume | 70 l | ||||||||||||||||||||
Setpoint 1 | +20 °C | ||||||||||||||||||||
Setpoint 2 | 0 °C | ||||||||||||||||||||
Reactor | 100l Büchiglas (glass) | ||||||||||||||||||||
Tubing length | 3 m | ||||||||||||||||||||
Fluid in unit | Thermal HL80 | ||||||||||||||||||||
Fluid in reactor | Thermal HL80 |
Environment
Room temperature | 20 °C |
---|---|
Humidity | 45 % |
Voltage version | 400V/3PNPE/50Hz |