Case Study: PRESTO W50 Process system

Heating up of an Büchiglas 100 l reactor from +20 °C to +100 °C with a PRESTO W50 Process system

Objective

This case study tests the heating capacity of the JULABO PRESTO W50 Process system with a 100 l glass reactor. The PRESTO W50 is connected to the reactor via two 2 in. metal hoses. The PRESTO W50 Process system has been programmed to heat up from +20 °C to +100 °C.

Test Conditions

Product PRESTO W50 Process system
Cooling capacity (Ethanol)
°C 20 0 -10 -20 -30 -40
kW 7.5 6.5 4.5 2.8 1.6 0.6
Heating capacity 6 kW
Pump pressure 7.3 psi Band limit °k
Duration 1:55 hr:min Test volume 80 l
Setpoint 1 +20 °C Setpoint 2 +100 °C
Reactor 100l Büchiglas (glass) Tubing length 2 in.
Fluid in unit Thermal HL60 Fluid in reactor Thermal HL60

Environment

Room temperature 20 °C
Humidity 45 %
Voltage version 400V/3PNPE/50Hz

Control Parameters

XP 0.2 K
TN 695 s
TV 85 s
XPU 15 K
PRESTO W50 details

Test Results

The PRESTO W50 Process system heats up the reactor from +20 °C to +100 °C in 1:55 h.

  • Set point
  • Temperature in the application
  • Temperature in temperature control unit