Case Study: PRESTO A45 Process system

Cooling a Chemglas 20 l reactor from +150 °C to +20 °C with a PRESTO A45 Process system

Objective

This case study tests the cooling capacity of the JULABO PRESTO A45 Process system with a 20 l glass reactor. The PRESTO A45 is connected to the reactor via two 2 in. long metal hoses. The PRESTO A45 Process system has been programmed to cool down from +150 °C to +20 °C.

Test Conditions

Product PRESTO A45 Process system
Cooling capacity (Ethanol)
°C 200 20 0 -10 -20 -30 -40
kW 3.4 3.5 3.3 2.6 1.8 1 0.3
Heating capacity 6 kW
Pump pressure 7.3 psi Band limit °k
Duration 59 hr:min Test volume 15 l
Setpoint 1 +150 °C Setpoint 2 +20 °C
Reactor 20l Chemglas (glass) Tubing length 2 in.
Fluid in unit Thermal HL60 Fluid in reactor Thermal H20S

Environment

Room temperature 20 °C
Humidity 45 %
Voltage version 400V/3PNPE/50Hz

Control Parameters

XP 0.19 K
TN 623 s
TV 83 s
XPU 20 K
PRESTO A45 details

Test Results

The PRESTO A45 Process system cools the reactor from +150 °C to +20 °C in 59 min.

  • Set point
  • Temperature in the application
  • Temperature in temperature control unit