Case Study: PRESTO W50t Process system
Cooling a QVF 30 l reactor from +20 °C to -20 °C with a PRESTO W50t Process system
Objective
This case study tests the cooling capacity of the JULABO PRESTO W50t Process system with a 30 l glass reactor. The PRESTO W50t is connected to the reactor via two 2 m long metal hoses. The PRESTO W50t Process system has been programmed to cool down from +20 °C to -20 °C.
Test Conditions
Product | PRESTO W50t Process system | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Cooling capacity (Ethanol)
|
|||||||||||||||
Heating capacity | 12 kW | ||||||||||||||
Pump pressure | 0.5 bar | ||||||||||||||
Duration | 1:01 hr:min | ||||||||||||||
Test volume | 22.5 l | ||||||||||||||
Setpoint 1 | +20 °C | ||||||||||||||
Setpoint 2 | -20 °C | ||||||||||||||
Reactor | 30l QVF (glass) | ||||||||||||||
Tubing length | 2 m | ||||||||||||||
Fluid in unit | Thermal HL60 | ||||||||||||||
Fluid in reactor | Thermal HL60 |
Environment
Room temperature | 20 °C |
---|---|
Humidity | 45 % |
Voltage version | 400V/3PNPE/50Hz |
Control Parameters
XP | 0.2 K |
TN | 695 s |
TV | 85 s |
XPU | 15 K |
Test Results
The PRESTO W50t Process system cools the reactor from +20 °C to -20 °C in 1:01 h.
Set point |
Temperature in the application |
Temperature in temperature control unit |