FC1200S Chiller
with increased pump capacity
Recirculating coolers of the FC series with an increased pump capacity are available for applications with large volumes. Thanks to their integrated heating, they have an increased working temperature range and operate very precisely with a temperature stability of ±0.2 °C.
Performance data depends on the mains voltage in the country of use. Please select:
| Order number including voltage version | 9600123.04 |
|---|---|
| Working temperature range | -15 ... 80 °C |
| Temperature stability | ±0.2 °C |
| Heating capacity | 1.2 kW |
| Pump capacity flow rate | 22 l/min |
| Pump capacity pressure | 1.2 bar |
| Filling volume | 8 ... 11 l |
|
Total dimensions
(W × L × H) |
46 x 61 x 49 cm |
Product Features
- Adjustable ratio for feed/return temperatures
- Easy filling system located at the front
- Activation of pump for filling
- Bright MULTI-DISPLAY (LED)
- Upper and lower temperature warning functions with interval tone
- Integrated freezing protection and dry-running protection
- Rapid and easy operation via seamless, splash-proof keypad
- Liquid level indication on the front
- Self-test, reciprocal sensor monitoring, pump motor and compressor overload protection
- Complete shut-down with audible signal in case of an alarm
- removable venting grid for simplified removal of dust
- RS232 interface for PC connection
- High temperature stability
- Integrated heater with 1.2 kW capacity
Technical data for FC1200S
|
Total dimensions (W × L × H) |
46 x 61 x 49 cm |
|---|---|
| Filling volume | 8 ... 11 l |
| Weight | 66 kg |
| Pump connections | M16x1 male |
| Barbed fittings inner diameter | 8/10 mm |
| Working temperature range | -15 ... 80 °C |
|---|---|
| Temperature stability | ±0.2 °C |
| Temperature display resolution | 0.1 °C |
| Ambient temperature | +5 ... +40 °C |
Performance data depends on the mains voltage in the country of use. Please select:
| Heating capacity | 1.2 kW | |||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Cooling capacity
1 Performance specifications measured in accordance with DIN 12876. Cooling capacities up to 20 °C measured with ethanol; over 20 °C with thermal oil unless otherwise specified. Performance specifications apply at an ambient temperature of 20 °C. Performance values may differ with other bath fluids. |
||||||||||||||||||||||
| Pump capacity flow rate | 22 l/min | |||||||||||||||||||||
| Pump capacity pressure | 1.2 bar | |||||||||||||||||||||
| Power consumption | 8 A | |||||||||||||||||||||
| Bath tank | Stainless steel |
|---|
| Cooling of compressor | 1-stage Air |
|---|
| Sound pressure level | 57 dB(A) |
|---|---|
| Classification according to DIN12876-1 |
Classification III (FL) |
| IP Code according to IEC 60529 |
IP 21 |
| Pump type | Immersion Pump |
| Interfaces | Alarm output / Profibus optional / RS232 / Stakei / Standby-Input |
|---|---|
| External pt100 sensor connection | not available |
| Temperature control | PID1 |
| Temperature display | 2x LED |
| Temperature setting | Keypad |
| 9600123.03 | 230V 50Hz (Schuko Plug - CEE 7/4 Plug Type F) (R134a) |
|---|---|
| 9600123.04 | 230V 50Hz (UK Plug Type BS1363A) (R134a) |
| 9600123.05 | 230V 50Hz (CH Plug Type T12 / 10A) (R134a) |
| 2 Barbed fittings for tubing 8 and 12 mm ID. (Pump connections M16x1 male) |
Accessory for FC1200S
Downloads for FC1200S
We would also be happy to send you our printed catalogs and brochures by post.
Request brochureFC1200S Benefits
100% Checked.
100% testing. 100% quality. Each JULABO Circulator undergoes thorough quality testing before leaving the factory.
Green technology.
Development consistently applied environmentally friendly materials and technologies.
100 % Cooling capacity
‘Active Cooling Control’ for cooling available throughout the entire working temperature range, fast cool-down even at higher temperatures
For flammable bath fluid
Classification III (FL) according to DIN 12876-1
Related Products
Products with similar properties