Case Study: PRESTO W50t Process system

Heating up of an Büchiglas 50 l reactor from -20 °C to +20 °C with a PRESTO W50t Process system

Objective

This case study tests the heating capacity of the JULABO PRESTO W50t Process system with a 50 l glass reactor. The PRESTO W50t is connected to the reactor via two 2 m metal hoses. The PRESTO W50t Process system has been programmed to heat up from -20 °C to +20 °C.

Casestudy-PRESTO-W50-Buechiglas-50-Liters-Reactor

Test Conditions

Product PRESTO W50t Process system
Cooling capacity (Ethanol)
°C 200 20 0 -10 -20 -30 -40
kW 7 7.5 6.5 4.5 2.8 1.6 0.6
Heating capacity 12 kW
Pump pressure 0.5 bar
Duration 33 hr:min
Test volume 37.5 l
Setpoint 1 -20 °C
Setpoint 2 +20 °C
Reactor 50l Büchiglas (glass)
Tubing length 2 m
Fluid in unit Thermal HL60
Fluid in reactor Thermal HL60

Environment

Room temperature 20 °C
Humidity 45 %
Voltage version 400V/3PNPE/50Hz

Control Parameters

XP 0.19 K
TN 695 s
TV 85 s
XPU 15 K

Test Results

The PRESTO W50t Process system heats up the reactor from -20 °C to +20 °C in 33 min.

Set point
Temperature in the application
Temperature in temperature control unit