FC600S Chiller

with increased pump capacity

Recirculating coolers of the FC series with an increased pump capacity are available for applications with large volumes. Thanks to their integrated heating, they have an increased working temperature range and operate very precisely with a temperature stability of ±0.2 °C.

Performance data depends on the mains voltage in the country of use. Please select:

Country of use | Mains voltage | Plug | JULABO voltage version code
FC600S
Order number including voltage version 9600063.03
Working temperature range -10 ... 80 °C
Temperature stability ±0.2 °C
Heating capacity 1.2 kW
Pump capacity flow rate 22 l/min
Pump capacity pressure 1.2 bar
Filling volume 6 ... 8 l
Total dimensions
(W × L × H)
36 x 54 x 49 cm
Arrange callback

Product Features

  • Adjustable ratio for feed/return temperatures
  • Easy filling system located at the front
  • Activation of pump for filling
  • Bright MULTI-DISPLAY (LED)
  • Upper and lower temperature warning functions with interval tone
  • Integrated freezing protection and dry-running protection
  • Rapid and easy operation via seamless, splash-proof keypad
  • Liquid level indication on the front
  • Self-test, reciprocal sensor monitoring, pump motor and compressor overload protection
  • Complete shut-down with audible signal in case of an alarm
  • removable venting grid for simplified removal of dust
  • RS232 interface for PC connection
  • High temperature stability
  • Integrated heater with 1.2 kW capacity

Technical data for FC600S

Dimensions and volumes
Total dimensions
(W × L × H)
36 x 54 x 49 cm
Filling volume 6 ... 8 l
Weight 44 kg
Pump connections M16x1 male
Barbed fittings inner diameter 8/12 mm
Temperature values
Working temperature range -10 ... 80 °C
Temperature stability ±0.2 °C
Temperature display resolution 0.1 °C
Ambient temperature +5 ... +40 °C

Performance data depends on the mains voltage in the country of use. Please select:

Country of use | Mains voltage | Plug | JULABO voltage version code
Performance values
Heating capacity 1.2 kW
Cooling capacity
Medium: Ethanol
°C 20 10 5 0 -10
kW 1 0.5 0.37 0.3 0.24 0.1
Refrigerant R134a
Global Warming Potential 1430
Filling weight 290 g
Carbon dioxide equivalent 0.4147 t

1 Performance specifications measured in accordance with DIN 12876. Cooling capacities up to 20 °C measured with ethanol; over 20 °C with thermal oil unless otherwise specified. Performance specifications apply at an ambient temperature of 20 °C. Performance values may differ with other bath fluids.

Pump capacity flow rate 22 l/min
Pump capacity pressure 1.2 bar
Power consumption 8 A
Bath
Bath tank Stainless steel
Cooling
Cooling of compressor 1-stage Air
Other
Sound pressure level 54 dB(A)
Classification
according to DIN12876-1
Classification III (FL)
IP Code
according to IEC 60529
IP 21
Pump type Immersion Pump
Electronics
Interfaces Alarm output / Profibus optional / RS232 / Stakei / Standby-Input
External pt100 sensor connection not available
Temperature control PID1
Temperature display 2x LED
Temperature setting Keypad
Available voltage versions
9600063.13 230V 60Hz (Nema N6-20 Plug) (R134a)
9600063.03 230V 50Hz (Schuko Plug - CEE 7/4 Plug Type F) (R134a)
9600063.04 230V 50Hz (UK Plug Type BS1363A) (R134a)
9600063.05 230V 50Hz (CH Plug Type SEV 1011) (R134a)
Included in delivery
2 Barbed fittings for tubing 8 and 12 mm ID. (Pump connections M16x1 male)

Accessory for FC600S

Downloads for FC600S

We would also be happy to send you our printed catalogs and brochures by post.

Request brochure

FC600S Benefits

100% Checked.

100% testing. 100% quality. Each JULABO Circulator undergoes thorough quality testing before leaving the factory.

Green technology.

Development consistently applied environmentally friendly materials and technologies.

100 % Cooling capacity

‘Active Cooling Control’ for cooling available throughout the entire working temperature range, fast cool-down even at higher temperatures

For flammable bath fluid

Classification III (FL) according to DIN 12876-1